Generator size calculator
Tick the appliances and systems you will run at the same time. This page adds their running watts, then the largest extra starting (surge) watts from one motor, then a 25% margin, and rounds up to a standard standby size: 10, 14, 18, 20, 22, 24, 26, or 32 kW.
- Check each load. Edit quantity, running watts, and starting watts if your nameplate differs.
- Central air uses 2, 3, or 4 tons. We do not list 5-ton: no cited wattage. Lights are LED bulbs, not rooms.
- Read total running watts, the largest surge item, required watts, and the recommended kW.
- Use Estimate the cost of this size to open the generator cost calculator with that kW filled in.
Required watts = sum of running watts + the largest (starting − running) among selected motors. Recommended kW = required × 1.25, rounded up to the next listed standby size.
What size generator do I need?
Size from the loads you will run at once, not from house square footage. Add every selected appliance’s running watts, then add the single largest extra starting watts (starting minus running) from a motor load such as an air conditioner or well pump. Multiply that required wattage by 1.25 so the unit runs at about 80% of rated output, then round up to 10, 14, 18, 20, 22, 24, 26, or 32 kW. A licensed electrician must confirm a permanent standby with an NEC load calculation.
Running watts vs starting watts
Running watts are the power a load draws while it is on. Starting watts, also called surge watts, are the brief extra draw when a motor starts. A refrigerator might run at 400 W and start at 1,200 W. Resistive loads such as an electric dryer, water heater, or space heater do not add extra starting watts on the charts we cite: starting equals running. This calculator adds only the largest extra start, not every motor at once, because motors are not assumed to start together.
Worked example: fridge, freezer, 3-ton AC, furnace, lights, TV
Worked example
Default job on this page: refrigerator 400 W running / 1,200 W starting; freezer 500 / 1,000; 3-ton central AC 3,500 / 6,000; furnace blower 800 / 1,600; 10 LED bulbs at 15 W; TV and internet 420 W.
Running: 400 + 500 + 3,500 + 800 + 150 + 420 = 5,770 W. Extra starts: 800, 500, 2,500, 800, 0, 0. Largest extra is the 3-ton AC, 2,500 W. Required = 5,770 + 2,500 = 8,270 W. With a 1.25 margin: 8,270 × 1.25 = 10,337.5 W, which rounds up to 14 kW. Ten kW (10,000 W) is short of that margin; 20 kW covers it.
Those wattages are the high end of cited ranges and are editable. Use Estimate the cost of this size for a 14 kW installed range. For the transfer switch, pad, and gas line, see the generator cost calculator.
Safety
A permanently installed standby generator must be sized and wired by a licensed electrician using an NEC load calculation. Never backfeed a home by plugging a generator into a dryer outlet or panel without a transfer switch: that can kill line workers and damage equipment. This page is a planning estimate from published appliance wattages, not an installation design.